What size cable for a 2000W inverter at 12V?

50mm² tinned marine battery cable (1 AWG), protected by a Class T 250A, for a 2 metre run.

Recommended cable

50mm² tinned marine battery cable

A 2000W inverter at 12V draws about 185.2A. The current rating is what decides the size here, not volt drop.

The answer, and how we got it

A 2000W inverter on a 12V system draws roughly 185.2A of DC current at full output, allowing for inverter efficiency. Over a 2 metre run, one way, that calls for 50mm² tinned cable.

DC current at full output185.2A
Recommended cable50mm² (1 AWG)
Volt drop over 2m0.308V, 2.57% of nominal
Cable rating, derated345A
Has to carry250A
Conductor temperature assumed35°C
FuseClass T 250A
HolderClass T fuse block, 225 to 400A

Worked for a single unbundled cable in a cabin, on the 10% general-circuit limit, with lead acid batteries. Note that the cable is sized to carry the fuse (250A), not just the load (185.2A): a fuse has to sit above the continuous current or it nuisance blows, and the cable has to carry the fuse or the fuse is not protecting it.

35mm² The size below. Not enough for this load once the fuse is taken into account.
70mm² The size above. Worth it on a longer run, in an engine bay, or bundled with other cables.

Your run is probably not exactly 2 metres

Length changes the answer more than anything else, and so does where the cable runs: a conductor at 60°C in an engine bay carries 15.7% more resistance than the same cable at 20°C.

Work out your actual run

Or go straight to a made-up 50mm² lead, cut, crimped with matched dies, heat shrunk and labelled.

BS EN ISO 13297:2021 requires that calculated volt drop does not exceed 10% of nominal voltage. For equipment vital to safety it requires that the equipment be supplied with the proper voltage to achieve its rated performance, and offers 3% as an acceptable figure for such equipment. An inverter feed is a general circuit, so this page works to 10%.

The derating we apply is ours, following ABYC E-11 practice. The manufacturer publishes a nominal current rating with no stated conditions. This is a design aid and not a design, and the installer remains responsible for the installation.

Figures generated from our live cable data and last reviewed 2 September 2026.